GD-35 UV Phototube UV Photosensitive Tube UV Detector Flame Detection Fire Alarm

GD-35-type photosensitive tubeis a glass structure with a cold cathode gas-filled Diode. The tube has the characteristics of high sensitivity and fast response, and is mainly used for ultraviolet flame detectors, electric spark monitoring and ultraviolet measurement. GD-35It has the same performance as Hamamatsu's R2868 and can be interchanged.

Classification:

CONTACT

Products Details

GD-35 type (foreign corresponding model R2868)

 

 

GD-35-type photosensitive tubeis a glass structure with a cold cathode gas-filled Diode.

The tube has the characteristics of high sensitivity and fast response, and is mainly used for ultraviolet flame detectors, electric spark monitoring and ultraviolet measurement.

GD-35It has the same performance as Hamamatsu's R2868 and can be interchanged.

 

a, external dimensions

Photosensitive tubeHeight (H)  36< span>mm(max)

Photosensitive tubeOuter diameter (D)  < span>Φ(9±1)mm

Pin length (L)     20mm

 

b, main parameters

1, spectral response range185nm260nm

2, peak wavelength210nm

Parameters

Unit

Minimum

Maximum

Anode voltage

V

300

350

Peak current

mA

 

3

Average output current

mA

 

1

Ambient temperature

°C

-30

80

 

c, working conditions and typical characteristics (25°C)

Parameters

Unit

Minimum

rated

Maximum

Starting voltage

V

 

 

220

Pipe pressure drop

V

 

 

200

Working voltage range

V

300

325

350

Average output current

mA

 

0.3

 

Sensitivity

cps

 

5000

 

Background (count rate)

cps

 

 

10

Average life span

h

 

10000

 

 

Introduction to Ziguang photoelectric tube:< /span>

   When light hits the photocathode, the photocathode excites photoelectrons into the tube, These electrons move towards the anode under the action of the electric field, and ionize due to collision with the gas atoms in the tube  In the process of ionization, new electrons and photoelectrons are all received by the anode, but positive ions move in the opposite direction and are received by the cathode. Therefore, in the entire circuit, there is a photocurrent that is several times that of a vacuum phototube. The main application of UV phototubes is the photoelectric effect of metal and the multiplication effect of gas, which can well detect the ultraviolet radiation in the 185~290nm spectral range and generate photocurrent. It is not sensitive to radiation outside this spectral region, such as visible sunlight and indoor lighting sources. Therefore, it is not necessary to use a visible light shield like other semiconductor devices, so it is more convenient to use.

The ultraviolet phototube can detect weak ultraviolet radiation, and can be used in boiler oil, gas monitoring, and fire alarms. , The power system conducts lightning protection monitoring for unattended transformers, etc.

 

Features of UV photocells:

1. Ultraviolet radiation with very weak detection;

2, does not respond to visible light and infrared;

3, high reliability and long life;

4, high response speed;

5, low current operation;

6, light weight.

 

Second,  Application of UV phototubes:

1. Boiler oil and gas monitoring device; 2. Fire alarm device; 3. Ultraviolet light leakage monitoring device; 4. Automatic equipment control Devices; 5. UV monitoring devices for aircraft engines and cabins; 6. Three defense systems for tanks and other armored vehicles.

3. How to install UV photoelectric tube< /span>

The UV photoelectric tube and the system are generally connected by a tube socket (as shown in the figure below). If the connection is made by welding, please pay special attention to the welding temperature at the pins not to exceed 250℃, otherwise the glass bulb may explode and crack.

The glass protruding part (exhaust pipe) between the pins shall not be subjected to force or collision, so as to prevent the pipe from leaking and failing.

When inserting or pulling out the socket, force must be perpendicular to the socket, and do not break or twist. Cause damage.

Electrode connection method: Use the correct connection method to connect the UV phototube electrode, if the electrode connection is opposite, it may cause malfunction Or the signal is weak.

Four. Instructions for use of UV photocells:

The tube must be wiped clean before use, especially the top of the tube must not have oil, dust and other dirt sticking to it, otherwise it will Affect its performance.

The working voltage of the tube must not exceed the specified MAX working voltage, otherwise it may affect the working performance and life of the tube . The pins can be soldered, and the soldering temperature should not exceed250 Spend.

The working voltage must be stable, otherwise it is easy to cause the pipe parameter change or use failure.